Volvo Penta TAD1344GE 450 kVA Diesel Generator

Volvo Penta TAD1344GE 450 kVA Diesel Generator

Description
Download PDF

Volvo Penta TAD1344GE 450 kVA Diesel Generator

Ratings & Electrical

  • Prime Power: 360 kW / 450 kVA
  • Standby Power: ~396 kW / 495 kVA
  • Frequency: 50 Hz
  • Speed: 1500 rpm
  • Voltage: 400/230 V (3-phase)
  • Power Factor: 0.8 (lagging)
  • Alternator Insulation: Class H
  • Voltage Regulation: ±1%

Engine / Mechanical

  • Engine Model: Volvo TAD1344GE
  • Configuration: 4-stroke, 6-cylinder, inline, turbocharged & aftercooled
  • Displacement: 10.2 L
  • Bore × Stroke: 108 mm × 130 mm
  • Compression Ratio: 17.5 : 1
  • Lubricating Oil Capacity: ~35 L
  • Coolant Capacity: ~50 L

Fuel & Consumption

  • Fuel Type: Diesel
  • Fuel Consumption @100% Load: ~88 L/h
  • Fuel Consumption @75% Load: ~66 L/h
  • Fuel Tank Capacity: ~950 L (typical enclosure)

Cooling, Exhaust & Air

  • Exhaust Gas Temperature: ~520 °C
  • Exhaust Gas Flow: ~45 m³/min
  • Max Exhaust Back Pressure: 10 kPa
  • Cooling System: Radiator-cooled, tropical rating

Physical Dimensions & Weight

  • Dimensions (L × W × H): ~3700 mm × 1800 mm × 2200 mm
  • Weight (approx.): ~4000 kg (open set)

Alternator & Control

  • Alternator Frame: Stamford or equivalent, Class H insulation
  • Control Panel: Volvo/DeepSea electronic controller
  • Features: Monitoring, protection & optional auto-start/stop
×